BIS Certification for Cables and Wires in India
Every electrical cable on BIS's compulsory lists needs an ISI mark licence, but the standard depends on the cable. House wiring and flexible cords come under IS 694, PVC power cables under IS 1554, XLPE cables under IS 7098, and solar DC and fire survival cables under their own 2023 order. USB and data cables are not covered.
BIS for cables and wires?
Tell us the product and we'll confirm which rule applies.
Updated 10 November 2026. Checked against the BIS lists of products under compulsory certification and the orders in the Gazette of India.
Which BIS rule applies to your cable
| Cable | What it needs | Indian Standard | Notified under |
|---|---|---|---|
| PVC house wiring and flexible cords, rigid or flexible conductor, up to 1,100 V | ISI mark licence | IS 694:2010 | S.O. 189(E), 17 February 2003, as amended |
| PVC insulated heavy duty power and control cables up to 1,100 V | ISI mark licence | IS 1554 (Part 1) | Cables (Quality Control) Order, 2020, S.O. 280(E), 21 January 2020 |
| PVC heavy duty cables, 3.3 kV to 11 kV | ISI mark licence | IS 1554 (Part 2) | S.O. 280(E) |
| XLPE cables up to 1,100 V | ISI mark licence | IS 7098 (Part 1), 2025 edition | S.O. 280(E) |
| XLPE cables, 3.3 kV to 33 kV | ISI mark licence | IS 7098 (Part 2) | S.O. 280(E) |
| XLPE cables, 66 kV to 220 kV | ISI mark licence | IS 7098 (Part 3) | S.O. 280(E) |
| Aerial bunched cables up to 1,100 V | ISI mark licence | IS 14255 | S.O. 280(E) |
| Elastomer insulated cables up to 1,100 V | ISI mark licence | IS 9968 (Part 1), 2025 edition | S.O. 189(E) |
| Elastomer insulated cables, 3.3 kV to 33 kV | ISI mark licence | IS 9968 (Part 2) | S.O. 280(E) |
| Halogen free flame retardant (HFFR) cables up to 1,100 V | ISI mark licence | IS 17048 | S.O. 280(E) |
| Welding cables | ISI mark licence | IS 9857 | S.O. 280(E) |
| Elastomer insulated flexible cables for mines | ISI mark licence | IS 14494:2019 | S.O. 280(E) |
| Flexible cables for miner’s cap lamps | ISI mark licence | IS 2593 | S.O. 280(E) |
| Shot firing cables (other than in shafts) | ISI mark licence | IS 5950 | S.O. 280(E) |
| Thermocouple compensating cables | ISI mark licence | IS 8784 | S.O. 280(E) |
| Solar DC cables for PV systems, 1,500 V DC | ISI mark licence | IS 17293:2020 | Solar DC Cable and Fire Survival Cable (Quality Control) Order, 2023, S.O. 3807(E) |
| Fire survival cables up to 1,100 V AC and 1,500 V DC | ISI mark licence | IS 17505 (Part 1):2021 | S.O. 3807(E) |
| USB, charging and data cables | No compulsory BIS certification | Voluntary | Not on any BIS list |
All of these are Scheme-I products. BIS grants the licence to the manufacturer for one factory and one Indian Standard, inspects the factory, has samples tested at a BIS or BIS-recognised laboratory, and the cable then carries the ISI mark with the IS number and the CM/L licence number. Overseas factories apply under the Foreign Manufacturers Certification Scheme (FMCS) and nominate an Authorised Indian Representative. The licence lists the cable types and sizes it covers, so a licence for one type of cable does not cover another.
House wiring and flexible cords: IS 694
IS 694:2010 covers PVC insulated unsheathed and sheathed cables and cords, with rigid or flexible conductors, for voltages up to and including 1,100 V. It is the standard for house wire and for flexible cords. It is notified under the oldest electrical order, the Electrical Wires, Cables, Appliances and Protection Devices and Accessories (Quality Control) Order, 2003 (S.O. 189(E), 17 February 2003, as amended), which also covers switches, MCBs and RCCBs.
It is also the most licensed cable standard by far. BIS’s records show 1,310 licences for IS 694, 1,241 of them operative, with the most in Delhi, Gujarat and Uttar Pradesh. BIS’s product manual asks for a 25 m sample. Aaditech has secured 60+ licences for PVC insulated cables so far.
Power and control cables: IS 1554 and IS 7098
The Cables (Quality Control) Order, 2020 (S.O. 280(E), 21 January 2020) brought the armoured and unarmoured power and control cables used in buildings, industry and distribution networks under the ISI mark:
- PVC insulated heavy duty cables, IS 1554: Part 1 up to 1,100 V and Part 2 from 3.3 kV to 11 kV. BIS’s records show 334 licences for Part 1 and 13 for Part 2.
- XLPE insulated cables, IS 7098: Part 1 up to 1,100 V, Part 2 from 3.3 kV to 33 kV and Part 3 from 66 kV to 220 kV. IS 7098 (Part 1) was revised in 2025, and the order applies the latest version of each standard as BIS notifies it. BIS’s records show 413 licences for Part 1, 91 for Part 2 and 21 for Part 3.
The same order covers aerial bunched cables to IS 14255 (267 licences), elastomer insulated cables from 3.3 kV to 33 kV to IS 9968 (Part 2), and halogen free flame retardant cables up to 1,100 V to IS 17048 (62 licences). Elastomer cables up to 1,100 V, IS 9968 (Part 1), were already covered by the 2003 order; that standard too was revised in 2025.
Aaditech has secured 25+ licences for XLPE power cables.
Special-purpose cables
Five smaller cable types are also in the 2020 order, each with its own standard and licence:
- Welding cables, IS 9857. BIS’s records show 50 licences.
- Elastomer insulated flexible cables for use in mines, IS 14494:2019.
- Flexible cables for miner’s cap lamps, IS 2593. BIS published a second revision in 2023.
- Shot firing cables for use other than in shafts, IS 5950, revised in 2024.
- Thermocouple compensating cables, IS 8784.
Solar DC cables and fire survival cables
The Solar DC Cable and Fire Survival Cable (Quality Control) Order, 2023 (S.O. 3807(E), 24 August 2023) came into force six months after its publication. It covers two cables:
- Solar DC cables: electric cables for photovoltaic systems rated 1,500 V DC, to IS 17293:2020. BIS’s records show 50 licences.
- Fire survival cables: thermosetting insulated cables for working voltages up to 1,100 V AC and 1,500 V DC, to IS 17505 (Part 1):2021. BIS’s records show 38 licences.
Like the 2020 cables order, it does not apply to cables made in India for export.
Cable materials with their own orders
Several materials that go into cables need the ISI mark under orders of their own, so a cable maker should buy them from licensed suppliers:
- Galvanised steel armour wires, formed wires and tapes, IS 3975, under the Steel and Steel Products order. BIS’s product manuals for IS 1554, IS 7098 and IS 17505 list IS 3975 armour as a raw material. See GI armour wires and tapes.
- Poly-laminated aluminium cable wrap, IS 16012:2012, under the Electrical Accessories (Quality Control) Order, 2023. See cable wrap.
- Copper wire rods for electrical applications, IS 12444:2020, under the Copper Products order. See copper wire rods.
- EC grade aluminium rod, IS 5484, and wrought aluminium wire for electrical purposes, IS 2067, under the Aluminium and Aluminium Alloy Products (Quality Control) Order, 2026 (S.O. 1319(E)): the rod with immediate effect, the wire from 1 December 2026 (1 March 2027 for small and 1 June 2027 for micro enterprises). See EC grade aluminium rod and aluminium wire for electrical purposes.
Steel wire ropes, steel wire strands and steel wire for concrete are a different family altogether, with their own entries on BIS’s list, not under the cable orders.
Cables that do not need BIS
- USB, charging and data cables are not on the CRS list or any Quality Control Order. BIS has published USB standards, such as IS/IEC 62680 for USB cables and connectors, but no order makes them compulsory. See is BIS required for USB cables.
- Cables to standards no order names are not on BIS’s compulsory lists. Examples in our test scope are IS 4289 for flexible lift cables and IS 2465 for cables for motor vehicles.
- Bare overhead conductors to IS 398 are not on BIS’s lists, though EC grade aluminium rod (IS 5484) is, and aluminium wire for electrical purposes (IS 2067) will be from 1 December 2026.
- Cables made in India for export are outside the 2020 cables order and the 2023 solar DC and fire survival cable order.
Power cords supplied with products under CRS registration, such as adaptors and monitors, are among the typical safety critical components in MeitY’s CRS FAQs. A safety critical component of a registered product may be replaced only with one of the same rating, and the change must be informed to BIS.
Testing
An ISI application is backed by a test report from a laboratory that BIS has recognised for that standard. BIS recognises 50 laboratories for IS 694, 45 for IS 1554 (Part 1), 42 for IS 7098 (Part 1) and 10 for IS 17293. A full type test covers the conductor, dimensions, insulation and sheath before and after ageing, armour, electrical tests and, for flame retardant cables, fire performance. Our cable type test list explains each test and the IS 10810 method behind it.
Aaditech offers NABL accredited cable and wire testing, with testing available at a BIS-recognised laboratory for IS 694, IS 1554, IS 7098, IS 9968, IS 14255, IS 17048, IS 17293, IS 17505, IS 14494 and IS 9857. The same report can usually go with a utility or PSU tender; see NABL accredited vs BIS-recognised lab.
BIS product pages for cables and wires
- PVC Insulated Cables (up to 1100 V) ISI mark licence (Scheme-I) · IS 694
- PVC Power Cables (up to 1100 V) ISI mark licence (Scheme-I) · IS 1554(Part 1) : 1988
- PVC Power Cables (3.3 to 11 kV) ISI mark licence (Scheme-I) · IS 1554(Part 2) : 1988
- XLPE Cables (up to 1100 V) ISI mark licence (Scheme-I) · IS 7098 (Part 1) : 1988
- XLPE Cables (3.3 to 33 kV) ISI mark licence (Scheme-I) · IS 7098 (Part 2) : 2011
- XLPE Cables (66 to 220 kV) ISI mark licence (Scheme-I) · IS 7098 (Part 3) : 1993
- Aerial Bunched Cables (up to 1100 V) ISI mark licence (Scheme-I) · IS 14255 : 1995
- Elastomer Insulated Cables (up to 1100 V) ISI mark licence (Scheme-I) · IS 9968 (Part 1)
- Elastomer Insulated Cables (3.3 to 33 kV) ISI mark licence (Scheme-I) · IS 9968 (Part 2) : 2002
- HFFR Cables (up to 1100 V) ISI mark licence (Scheme-I) · IS 17048 : 2018
- Welding Cables ISI mark licence (Scheme-I) · IS 9857 : 1990
- Flexible Mining Cables (Elastomer) ISI mark licence (Scheme-I) · IS 14494 : 2019
- Flexible Cables for Miner’s Cap-Lamps ISI mark licence (Scheme-I) · IS 2593 : 1984
- Shot Firing Cables ISI mark licence (Scheme-I) · IS 5950 : 1984
- Thermocouple Compensating Cables ISI mark licence (Scheme-I) · IS 8784 : 1987
- Solar DC Cables (1500 V) ISI mark licence (Scheme-I) · IS 17293:2020
- Fire Survival Cables ISI mark licence (Scheme-I) · IS 17505(Part 1): 2021
- Poly- Laminated Aluminium Cable Wrap ISI mark licence (Scheme-I) · IS 16012: 2012
Frequently asked questions
Is BIS certification mandatory for electrical wires and cables in India?
For the cables on BIS's Scheme-I list, yes. They need an ISI mark licence: PVC house wiring and flexible cords to IS 694, PVC power cables to IS 1554, XLPE cables to IS 7098, aerial bunched cables to IS 14255, elastomer cables to IS 9968, HFFR cables to IS 17048, solar DC cables to IS 17293 and fire survival cables to IS 17505 (Part 1), along with welding, mining, shot firing and thermocouple compensating cables.
Which BIS standard applies to house wire?
IS 694:2010, for PVC insulated unsheathed and sheathed cables and cords with rigid or flexible conductors, up to and including 1,100 V. It is notified under the Electrical Wires, Cables, Appliances and Protection Devices and Accessories (Quality Control) Order, 2003, S.O. 189(E), as amended.
Do USB and charging cables need BIS certification?
No. USB, charging and data cables are not on the CRS list or any Quality Control Order. The cable orders cover power cables such as IS 694 and IS 1554. BIS has USB standards, such as IS/IEC 62680, but no order makes them compulsory.
Do solar DC cables need the ISI mark?
Yes. The Solar DC Cable and Fire Survival Cable (Quality Control) Order, 2023, S.O. 3807(E) of 24 August 2023, requires the ISI mark on electric cables for photovoltaic systems rated 1,500 V DC, to IS 17293:2020. The same order covers fire survival cables to IS 17505 (Part 1):2021.
Does one BIS licence cover all types of cable?
No. A licence is granted for one Indian Standard at one factory, and it lists the types and sizes covered. A licence for IS 694 house wire does not cover IS 1554 power cable or IS 7098 XLPE cable, so a maker of all three holds three licences.
Do armour wires and cable materials need BIS?
Some do, under their own orders. Galvanised steel armour wires and strips for cables need the ISI mark under IS 3975, poly-laminated aluminium cable wrap under IS 16012, and copper wire rod and EC grade aluminium rod for electrical use under IS 12444 and IS 5484.
Related pages
- Cable type test list: IS 694, IS 1554 and IS 7098
- NABL accredited cable and wire testing
- NABL accredited vs BIS-recognised lab
- Is BIS required for USB cables and phone accessories?
- Pre-dispatch inspection checklist for cables
- BIS for switches, MCBs, plugs and sockets
- How to check a BIS licence number
BIS lists checked 10 November 2026. Orders change often; confirm the current notification before applying.
Not sure which certification your product needs?
Talk to a team led by former BIS Directors. We'll map every approval your product needs before you spend on testing.